Assembled Data Center

All Products


undefined
+
  • undefined

Classification:

Assembled Data Center

1) External temperature: normal work under ambient temperature -20~50 ℃
2) Internal temperature: cold channel working temperature 18~27 ℃;
3) external relative humidity: 5% ~ 100 relative humidity under normal work (no condensation);
4) Internal relative humidity: maintain the dew point temperature of 5~15 degrees Celsius, the relative humidity is not more than 60%;
5) Altitude: less than 1000 meters (derating design should be considered when the altitude exceeds 1000 meters);
6) solar radiation intensity: solar radiation intensity is less than 1120W/m2 under the condition of normal work;
7) Seismic fortification intensity: 7 degrees (GB 50011-2010(2016 Edition) Code for Seismic Design of Buildings);
8) Pollution grade: Grade IV (climbing distance: 3.1cm/kV, based on the highest working voltage);9) Protection grade: IP55;

Prefabricated customized boxes are used, which are divided into low-voltage warehouse, medium-voltage warehouse, machine warehouse and spare parts warehouse according to different functions, including all power distribution units such as medium and low-voltage power distribution cabinets, transformers and various monitoring components in Shengdao. Decoration, equipment installation, wiring, system integration and debugging are completed in the factory. At present, there are mainly two types of container-type square warehouse and skid-type square warehouse.

 

Keywords: power distribution module container